Emergency lighting across the UK

Take the burden of emergency lighting compliance off your team.

Long-life emergency luminaires with automated testing and reporting. Fewer site walks, fewer battery swaps, and records ready when your auditor arrives for an inspection.

  • 12-year design life exit and emergency lights
  • 10-year warranty on the whole fitting, including the battery
  • Automated testing and reporting to support BS 5266-1
  • Wireless plug-and-play system with one single controller

We make emergency lighting easy. Contact us and find out how we can do this for you.

“A simple, reliable solution that solved our compliance issues, allowing us to focus on other critical tasks around the college.”

Carl Simpson, Property and Environment Manager, Activate Learning
Sound familiar?

Failed lights, battery replacements and compliance headaches.

Running emergency lighting across a busy estate eats time your team doesn’t have.

!

Fittings and batteries keep failing

Short-life batteries mean constant call-outs, replacements and access issues in occupied buildings.

!

Testing takes up the week

Walking every floor for monthly and annual tests ties up staff, often out of hours.

!

Records are hard to pull together

Paper logbooks and spreadsheets make it slow to show your fire risk assessor, auditor or insurer what has been done.

Is there a simpler way to stay in control?

Zoneworks HIVE

Less maintenance. Less administration.

HIVE automates the routine functional and full-duration tests on your emergency luminaires and logs every result, so the responsible person has an up-to-date record without anyone walking the building with a test key.

It runs over a wireless mesh network: one RF controller manages up to 1,000 fittings, with no extra routers, repeaters or data cables between fittings. That makes it practical for listed buildings, hospitals and campuses where new cabling is disruptive.

Up to 12-year design lifeFewer replacements over the life of the building
Automated testing and reportingScheduled tests, logged automatically
Real-time visibilitySee every fitting’s status and diagnostics
Less administrationRecords ready when you need them
HIVE software on a tablet showing an emergency luminaire’s status, test results and maintenance log
Side by side

Manual testing vs Clevertronics

The traditional wayThe Clevertronics way
TestingStaff walk every floor with a test key, often out of hoursAutomatic functional and duration testing to support BS 5266-1
ReplacementsBatteries and fittings replaced every few yearsUp to 12-year design life, with up to a 10-year warranty on the whole fitting, including the battery
FaultsFound during the next test, or after a failureReported in real time with diagnostics
RecordsPaper logbooks and spreadsheets compiled by handTest records generated automatically
Case study

How Activate Learning freed its team from battery replacements and compliance reporting.

Activate Learning, which runs City of Oxford College, moved its campus emergency lighting to Clevertronics luminaires monitored by HIVE, replacing manual testing and paper records.

Trusted across the UK

Relied on by some of the UK’s best-known buildings.

4,000+sites worldwide
1 million+fittings installed
Westminster Abbey
Whittington Health NHS Trust
Royal Holloway, University of London
Bournemouth University
citizenM hotels
Free site survey

Start with a chat.

Our UK team covers sites across the UK.

  1. Tell us about your site

    A few details about your building or estate. It takes under a minute.

  2. Talk to a specialist

    A Clevertronics specialist will get back to you within one working day.

  3. Get a free on-site survey

    If it helps, we’ll visit your site at no cost. Afterwards you’ll get a free lighting design and cost comparison report.

Clevertronics illuminated exit sign suspended from the ceiling of an office corridor

Send us a message today

We’ll reply within one working day.

Free download

Emergency lighting compliance checklist

A one-page summary of the routine checks recommended in BS 5266-1:2025 and BS EN 50172:2024, and the questions every responsible person should be able to answer.

Monthly

  • Brief functional test of every emergency luminaire and exit sign
  • Visual check: present, clean, undamaged, unobstructed
  • Failures recorded
  • Corrective actions logged

Annually & 5-yearly

  • Full rated-duration test
  • Battery duration confirmed
  • Degraded fittings identified
  • Remedial actions completed
  • Photometric verification every 5 years (new in 2025)

Records

  • Complete test history kept
  • Maintenance records up to date
  • Faults visible and tracked
  • Compliance demonstrable on request

Ask yourself

  • Could I show my last 12 months of test results today?
  • Do I know which fittings are failing right now?
  • How many staff hours does testing cost us?

Download the guide (PDF)   Message us today

FAQ

Common questions

Who installs and maintains the system?

Any qualified electrical contractor can install Clevertronics luminaires and the HIVE system, whether that’s your in-house team or your existing external provider. Clevertronics then commissions the system to make sure everything is working, and hands it over to you in full working order.

After handover, we provide free lifetime support for every HIVE system. That includes training for your team, software updates, and answers to any questions you have.

Who is responsible for emergency lighting compliance?

Under UK fire safety law, the person in control of the premises is responsible. That’s the “responsible person” under the Regulatory Reform (Fire Safety) Order 2005 in England and Wales, the “duty holder” in Scotland, and the “appropriate person” in Northern Ireland. They must make sure emergency lighting is provided where the fire risk assessment calls for it, and that it is tested, maintained and recorded. HIVE doesn’t take on that responsibility, but it makes the routine testing and record-keeping much easier to manage.

How much does it cost?

It depends on the size and layout of your site, the number of fittings, and whether you’re retrofitting or fitting out new space. We have a variety of product types and two ranges to choose from, so you can match the solution to your budget and the outcome you’re after:

  • L10 range: 12-year design life and a 10-year warranty
  • CLP range: 8-year design life and a 6-year warranty

Both warranties cover the whole fitting, including the battery. After your free site survey, we’ll send you a free lighting design and cost comparison report so you can see the options side by side before you commit to anything.

How much does the software licence cost?

Nothing. Unlike other testing and monitoring systems, there is no licence fee and no integrator costs for the HIVE software or system.

How does automatic testing work?

Each luminaire is connected to HIVE over a wireless mesh network. HIVE runs the routine tests set out in BS EN 50172 and BS 5266-1: a short functional test every month and a full rated-duration test every year. It records each result and flags any fitting that fails so it can be repaired. Full-duration tests can be scheduled for low-risk times, or staggered so that neighbouring fittings aren’t discharged at the same time. That matters because batteries need time to recharge after a test.

Does HIVE support BS 5266-1:2025?

Yes. HIVE is designed to carry out and record the routine monthly and annual tests recommended in BS 5266-1:2025 and BS EN 50172:2024, giving you a complete, time-stamped test history. The 2025 edition of BS 5266-1 puts greater emphasis on automatic test systems, especially in premises that stay occupied during a power failure. Compliance also depends on correct system design, installation, commissioning and maintenance by a competent person, and HIVE supports that work rather than replacing it.

Can it be retrofitted into an existing building?

HIVE is perfect for retrofits as it uses a wireless mesh, so there are no data cables to run between fittings, which keeps disruption low in occupied, heritage and listed buildings. The luminaires still need a suitable mains supply, and the layout should be designed to BS 5266-1:2025 and BS EN 1838:2024. Our survey takes this into account.

How long must emergency lighting last in a power cut?

BS 5266-1 recommends a minimum duration of 3 hours for most premises, including any with sleeping accommodation, places of entertainment, and buildings that may be reoccupied before the batteries have fully recharged. A 1-hour duration is only acceptable where the building is evacuated immediately and not reoccupied until the batteries have recharged. Your fire risk assessment determines which applies. All Clevertronics emergency luminaires are rated for 3 hours, so they meet the longer requirement wherever you use them.

How long do the fittings and batteries last?

It depends on the range you choose. The L10 range has a 12-year design life and a 10-year warranty, and the CLP range has an 8-year design life and a 6-year warranty. Both warranties cover the whole fitting, including the battery. Throughout its life, every fitting still needs to pass its annual 3-hour duration test, and HIVE shows you straight away if one doesn’t.

Can I see the whole system at once?

Yes. HIVE shows the status of every fitting, including on a floor plan view, so you can see faults and test results across a building or estate. HIVE can also be viewed across multiple sites in any location using our multi-site function.

How do I produce compliance records?

HIVE logs every test result automatically, giving you the routine test records for your emergency lighting logbook. BS 5266-1:2025 expects the logbook to hold more than test results, such as the design documentation, commissioning and verification certificates, repairs and alterations, and five-yearly photometric verification. HIVE keeps the testing part current, so the rest is quicker to keep together.

Do I still need to do physical checks?

Yes, though far fewer. Automatic testing replaces walking the building to test each fitting by hand, but BS 5266-1:2025 and BS EN 50172:2024 still expect:

  • regular visual checks that luminaires and exit signs are present, clean, undamaged and not obstructed, and that nothing in the building has changed what they need to cover
  • daily checks of the indicators on any central battery system (not needed for self-contained fittings)
  • an annual inspection by a competent person, and prompt repair of any failures HIVE reports
  • photometric verification every five years, which is new in the 2025 edition: measuring the actual light levels against the design

HIVE makes these checks quicker because you already know which fittings have passed or failed.

Find out how much time and money your site could save.

Remove your compliance burden today and free up your time and budget. Contact us for a no-obligation discussion. A specialist will reply within one working day.

Message us today

Or call our UK team on 01895 430 255

Call us Message us